FREE SHIPPING on orders OVER $250
Use code SHIP4FREE at checkout
Fast Lead Times | Fast Shipping
QT-IPS-60W-DR is one economical slim 60W DIN Rail power supply series, adapting to be installed on TS-35/7.5 or TS-35/15 mounting rails. This entire 48v DIN rail power supply series adopts the full range AC input from 90VAC to 264VAC.
QT-IPS-60W-DR is an industrial mount power supply designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 89%, the entire 48v DIN rail power supply series can operate at the ambient temperature between -40℃ to 70℃ under air convection. It is equipped with constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus make QT-IPS-60W-DR a very competitive 48v DIN rail power supply solution for industrial applications.
FEATURES
APPLICATIONS
TECHNICAL SPECIFICATIONS
Model |
QT-IPS-60W-DR |
|||
Output |
Group of Output |
1 |
||
DC Voltage |
48V DC |
|||
Default Output Voltage |
48.00-48.2V (VIN: 220VAC / LOAD: 0A) |
|||
Output Rated Current |
1.25A |
|||
Output Current Range |
0-1.25A |
|||
Output Rated Power |
60W |
|||
Total Peak Output Power |
Up to 90W (Sustainable time 10S/220VAC) |
|||
Peak Output Current |
1.5A(Sustainable time 10S/220VAC) |
|||
Ripple noise |
Peak - Peak ≤100mV (Test Method: The terminal shall be in parallel with capacitance of 0.1uF and 47uF, testing at 20MHz) |
|||
Output Regulation Range |
DC47~56V |
|||
Stabilized Voltage Precision |
±1% (@ 90-264Vac input, 100% load) |
|||
Line Regulation |
±0.5% (@ 90-264Vac input, 100% load) |
|||
Load Regulation |
±1% (@ 90-264Vac input, 100% load) |
|||
Temperature Coefficient |
±0.03%/℃ |
|||
Output Start Time |
< 1.5S @ 115VAC |
|||
Output Hold Time |
> 20ms @ 115VAC, |
|||
Voltage Overshoot |
≤5% |
|||
Input |
Input Voltage Range |
90~264VAC |
||
Input Rated Voltage Range |
100~240VAC |
|||
Frequency Range |
47Hz~63Hz |
|||
Rated Frequency |
50/60Hz |
|||
Starting Voltage |
90V AC |
|||
Efficiency |
> 85.0% @ 115Vac, > 89.0% @ 230Vac |
|||
Input Current |
< 1.40A @ 115Vac, < 0.80A @ 230Vac |
|||
Inrush Starting Current |
< 20A @ 115Vac, |
|||
Power Factor |
PF>0.6 (at full load) |
|||
Protection |
Output |
Over power |
78~97W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode: Swing machine, Self-recovery after over-power released.) |
|
Over voltage |
57~70V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit) Note: Do not use external voltage. |
|||
Over current |
1.5~1.875A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-current released.) |
|||
Short circuit |
It achieves the long-term short circuit by connecting a sufficient cross-sectional area copper cable (Length at 15cm±5cm) with power output port. Self-recovery to normal after removing the short circuit. |
|||
Operation Environment |
Operation Temperature and Humidity |
-40~70℃; 20%~95%RH |
||
Storage Temperature and Humidity |
-40℃~85℃; 10%~95%RH non-condensing |
|||
Liberation |
Frequency range: 10 ~ 500Hz, Acceleration: 2G, Each sweep cycle 10min. Six sweeps along the X, Y, and Z axis |
|||
Surge |
Acceleration: 20G, Duration time: 11mS, Three shocks along X, Y and Z axis |
|||
Altitude |
2000m |
|||
Safety and EMC Standard @25℃ |
Security Standard |
GB4943/EN60950 â– Reference â–¡Certification |
||
Dielectric Strength |
Input—Output:3KVAC/10mA; Input--Case:1.5KVAC/10mA; Output---Case:0.5KVDC/10mA Time for each testing is 1min. |
|||
Grounding Test |
Test Condition: 32A/2min; Ground bond: <0.1 ohms. |
|||
Leakage Current |
Input to GND ≤3.5mA; Input to output ≤0.25mA (Input 264Vac, 63Hz) |
|||
Insulation Resistance |
Input—Output: 10M ohms; |
|||
EMI |
Conducted Interference |
EN55022, EN55024, FCC PART 15 CLASS B |
||
Radiated Interference |
EN55022, EN55024, FCC PART 15 CLASS B |
|||
Harmonic current |
EN61000-3-2 CLASS D |
|||
EMS |
Conducted Emission |
EN61000-4-6 Level3 |
||
Radiated Emission |
EN61000-4-3 Leve3 criterion B |
|||
Power Frequency Emission |
EN61000-4-8 Level3 |
|||
Electrostatic Emission |
EN61000-4-2 Level4 criterion B |
|||
EFT |
EN61000-4-4 Level4 criterion B |
|||
Surge |
EN61000-4-5 Level4 criterion B |
|||
Dip and Interruption |
EN61000-4-11 |
|||
Dimension (L*W*H) |
95.95*102.5*41mm |
Block Diagram
Derating Curve
PC
Availability: Usually ships within 24 hours.
Urgent Orders: Read Information
This video quickly and easily shows how to extend your network with fiber optic cabling using media converters or Ethernet switches.